seegongsik
Saved words
PW-C5 · Transmission and per-unit

Distribution systems: buying reliability with wire

Even delivering power to the same customers, how you weave the grid greatly changes how much a single fault cuts off. Switch with the tabs from a one-way radial to a closed loop to a meshed network, and learn the bargain of buying reliability with the cost of wire and switchgear.

Switch the grid and watch the outage shrink

For one and the same fault (red ✕), switch the grid. Radial darkens everything downstream of the fault, the loop back-feeds from the other side so only one section drops, and the network reroutes so no one loses power. The lit dots are customers receiving power.

Tap to switch the distribution system.
Customers interrupted by a single fault
4 / 8
One way out, so all downstream is cut. Cheapest but least reliable.
Wide outage

Radial · simple and cheap

The substation branches out one way to reach customers. It uses the least wire, so it is cheap, and its protection coordination is simple. But if any one point faults, every customer strung below it loses power. It is widely used in low-density rural areas and where reliability demands are modest.

Loop · opening a second path

Tie the two ends of a radial line into a loop and every customer gains a path from both left and right. Normally one point is kept open; on a fault the faulted section is cut at both sides and the open point is closed to feed from the other direction. So the outage is trapped in the faulted section and most customers are quickly restored. It costs more wire and switchgear but raises reliability greatly. It is the staple of urban distribution.

Observeradial: out = Ndown
Radial cuts off everything downstream of the fault.
Chooseloop: out = ?
The loop back-feeds, so only the faulted section.
Fill inmesh: out = ?
The network reroutes, so no outage.
On your ownpaths ↑ → cost ?
Raising reliability raises the equipment cost.

Network · a mesh, no outage

Several substations bind customers through several paths into a mesh. If any one path faults, the rest immediately carry the load, so outages are almost none. It is the most reliable but its wiring, protection and operation are the most complex and costly, so it is used for the cores of big cities and for critical loads like hospitals and data centers that can hardly tolerate an outage. At the service entrance, meanwhile, power splits into single-phase two-wire (home lighting and outlets), three-phase three-wire (motors) and three-phase four-wire (mixed single- and three-phase in commercial buildings).

Back to the first screen

It was a fault at one and the same point, yet under radial half the downstream went dark, under the loop only one section, and under the network no one. What changed was not the fault but whether the power had another path to take. Each extra path you open shrinks the harm of a single fault but raises the cost of wire and switchgear. Distribution design is, in the end, deciding how much reliability a given area needs and at what cost to buy it.

The distribution systems — the grid topology sets how far a single fault cuts power. Radial (one way): cheap but all downstream is cut. Loop (ring): back-fed, only the faulted section drops. Network (mesh): rerouted, no outage, most expensive. More paths is a trade of reliability up for cost up. The service entrance splits into single-phase two-wire, three-phase three-wire and three-phase four-wire.
The next step

We have seen transmission and distribution — the paths that send and divide power. The next section D looks at how power actually flows over those paths, and how they are protected when something goes wrong. The first unit (PW-D1) is power flow: once each bus’s voltage magnitude and angle are set, the active and reactive power on each line follow, and we trace how that flow is pushed along by the phase-angle difference.